Intumescent
An intumescent is a substance which swells as a result of heat exposure, thus increasing in volume, and decreasing in density. Intumescents are typically used in passive fire protection and, in America, require listing and approval use and compliance in their installed configurations in order to comply with the law.
Contents
Types of intumescents
Soft char producers
These intumescents produce a light char, which is a poor conductor of heat, thus retarding heat transfer. Typically, these materials also contain a significant amount of hydrates. As the hydrates are spent, water vapour is released, which has a cooling effect. Once the water is spent, it is only the insulation characteristics of the char that was produced, which can slow down heat transfer from the exposed side to the unexposed side of an assembly. Soft char producers are typically used in thin film intumescents for fireproofing of structural steel as well as firestop pillows. Typically, the expansion pressure that is created for these products is very low, because the soft carbonaceous char has little substance, which is beneficial if the aim is to produce a layer of insulation.
Hard expanding char producers
Harder chars are produced with sodium silicates and graphite. These products are suitable for use in plastic pipe firestops as well as exterior steel fireproofing. In those applications, it is necessary to produce a more substantial char, with a quantifiable expansion pressure. In the case of the firestops, a melting, burning plastic pipe must be squeezed together and shut so that there will be no hole for fire to go through an opening in an otherwise fire-resistance rated wall or floor assembly. In the case of the exterior fireproofing, a hydrocarbon fire must be held off with quite potentially more kinetic energy than a house fire. Intumescents that produce hard chars are not typically used for interior spray fireproofing as they are not suitable for that application.
Uses of intumescents in passive fire protection
Applications
- firestopping
- fireproofing
- gasketing applications
- windows
Occupancies
Problems with intumescents
Some intumescents are susceptible to environmental influences such as humidity, which can reduce or negate their ability to function. DIBt approvals quantify the ability of intumescents to stand the test of time against various environmental exposures. DIBt approved firestops and fireproofing materials are available in Canada and the U.S.[1]
Gallery
- Intumescent.jpg
Low Pressure Intumescent Resin: This product is suitable for use in passive fire protection in general, firestopping and interior fireproofing in particular. The small, orange chunk on the bottom right hand side is capable of growing into that large black shape. This type of intumescent is typically highly endothermic. It contains a lot of chemically bound water, in hydrates. As this is released, it cools adjacent materials. Such intumescents are useful as ingredients in firestop pillows and in paints, which are used for fireproofing purposes. These intumescents do not produce enough expansion force to be used in plastic pipe devices, where the intumescent must squeeze a melting plastic pipe or conduit shut.
- Unitherm.jpg
Pipes covered with a thin-film intumescent spray fireproofing product called unitherm. As the flame from the blow-torch is applied, the intumescent sodium silicate expands, forming a layer of insulation, which slows down heat transfer to the pipe below. Hydrates within the coating give up their water content, maintaining a temperature near the boiling point of 100°C. The critical steel temperature is ca. 540°C. Once the water is spent and enough heat has gone through the char, the steel can reach and exceed its critical temperature and then lose its strength. The time this takes determines the fire-resistance rating.
- Unitherm2.jpg
In this picture, the flame has been removed after the thin-film intumescent spray fireproofing product has been completely expanded. Some intumescents can undergo shrinkage shortly after full expansion has taken place. The important thing to remember, however, is the need for listing and approval use and compliance of the installed configuration.
- Int3.jpg
Intumescent gasketing used in passive fire protection, for fire door applications. Typically, such gasketing is needed to pass positive pressure furnace testing, a recent change in North America.
- Intfirestop.jpg
Intumescent putty, permanently pliable, used in a cable penetration firestop. Permanently pliable putties are similar in consistency to play-dough used for children's toys. Putties of this nature also lend themselves to be used as pads to cover electrical outlet boxes inside drywall assemblies required to have a fire-resistance rating. The endothermic and insulative action of the pads reduce thermal transfer through the metallic outlet box to the unexposed side of the rated drywall assembly. All intumescents must be installed in a manner consistent with listing and approval use and compliance requirements.
- Palusolmanschette.jpg
A passive fire protection example of an intumescent with strong expansion pressure. This intumescent is called Palusol. It is based on waterproofed sodium silicate. Another high-expansion intumescent popular for use in plastic pipe firestop devices is graphite. Graphite tends to be less affected by atmospheric conditions than many water-bearing intumescents.
- Ulc prueflingsaufbau.jpg
Construction of a test sample, consisting of a mock-up concrete floor frame, complete with penetrants. The concrete frame measures approximately 5’ x 9’ x 4" (ca. 1.5m x 2.3m x 10cm). It has a large hole in the centre with many mechanical and electrical services traversing. The penetrants extend 1’ (30cm) into the furnace and 3’ (91cm) on the unexposed side. A firestop mortar is being applied here. Notice the intumescent wrap strip surrounding the fibreglass pipe insulation. When the fire starts, this embedded intumescent will swell to take up the place of the melting insulation. The test was conducted in accordance with the Canadian firestop test method ULC in Scarborough, Ontario.[2]
References
Cite error: Invalid <references>
tag;
parameter "group" is allowed only.
<references />
, or <references group="..." />
See also
External links
- "The proof is in the fire" Chemical Innovation Magazine, American Chemical Society
- Article about intumescent materials
- Translation of DIBt test procedure for intumescent building products
- Translation of DIBt test procedure for reactive spray fireproofing materials
- American Chemical Society: Fire Retardancy of Polypropylene Composites Using Intumescent Coatingsde:Intumeszenz